WARNINGS
Benson equipment must be installed and maintained in accordance with the relevant
provisions of the Gas Safety (Installations and Use) Regulations 1998 for gas fired products.
Due account should also be taken of any obligations arising from the Health and Safety at
Works Act 1974 or relevant codes of practice. In addition the installation must be carried out
in accordance with the current IEE wiring regulations (BS 7671), BS 6896 (Industrial &
Commercial) and any other relevant British Standards and Codes of Practice by a qualified
installer. All external wiring MUST comply with the current IEE wiring regulations.
INSTALLATION & SERVICING MANUAL FOR
B
ENSON VARIANTE² TUBULAR HEATER
NATURAL GAS (G20 I
2
H), PROPANE GAS (G31 I
3
P)
Technical Support:
Tel: 01384 489200
AmbiRad Limited, Fens Pool Avenue, Brierley Hill, West Midlands, DY5 1QA
Seitenansicht 0
1 2 3 4 5 6 ... 71 72

Inhaltsverzeichnis

Seite 1 - VARIANTE² TUBULAR HEATER

1 WARNINGS Benson equipment must be installed and maintained in accordance with the relevant provisions of the Gas Safety (Installations and

Seite 2

10 Model 12 20 30 42 50 60 72 95 120 145 Above 300 300 300 300 300 300 300 300 300 300 Below 300 300 300 300 300 300 300 30

Seite 3 - Section Contents Page No

11 2.3 Warm Air Circulation The air heater should be positioned to enable maximum circulation of discharged warm air within the area to be heat

Seite 4

12 2.4.1.2 Mechanical Ventilation to the Heated Space In the event that the heater(s) are to be installed without the positive connection of combusti

Seite 5 - 1.0 Compliance notices

13 be within 1000 mm of floor level for natural gas and ideally at floor level for l.p.g gas installations but in any event no higher than 250 mm. 2

Seite 6

14 The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally

Seite 7

15 operation should mechanical air supply fail for any reason The table below provides specific data for each heater model as - 2.5 Flue Installa

Seite 8

16 For vertical flue installations the flue should rise vertically where possible bends should not exceed 45° and the number of bends should be kept

Seite 9

17 C32 Vertical Co axial flue kit options L1 maximum combined flue length 6 metres Kit comprises Item (1) Co-axial flue terminal Ø 80 x Ø 80 Ite

Seite 10 - 2.2 Heater Mounting

18 C32 Vertical Co axial flue kit options L1 maximum combined flue length 10 metres Kit comprises Item (1) Co-axial flue terminal Item (2) Ø100 x 25

Seite 11

19 L1 maximum combined flue length 10 metres Kit comprises Item (1) Co-axial flue terminal Item (2) Ø130 x 250 mm pipe x 2 Item (3) 900 by Ø130 be

Seite 13 - Heaters

20 Heater Unit Flue Exit HORIZONTAL Flue Exit VERTICAL MIN. MAX. MIN. MAX. 12 m 1,00 3,00 1,00 5,00 20 m 1,00 6,00 1,00 10,00

Seite 14

21 Heater Unit Horizontal L1 MIN Concentric Flue Combined Length L1MAX. 12 m 0.50 3.00 20 m 0.50 6.00 30 m 0.60 6.00 42 m 0.70 6.00 50 m

Seite 15 - 2.5 Flue Installation

22 VRE Flueing options B22 Single pipe flue only and C32 Vertical coaxial Heater Unit Flue Exit Vertical Co/Axial Combined length Flue Exit

Seite 16

23 2.6 Electrical Installation All electrical wiring and connections must be in accordance with the relevant European, National, and Local regulati

Seite 17

24 Fan Control Relay The fan control switch features normally open 230V contacts, and is wired to control the live supply to the fan motor. When the

Seite 18

25 Each heater supply must be fitted with a separate isolating cock positioned adjacent to and upstream of the union which must be sited outside the

Seite 19

26 a) Test for earth continuity. b) Test for resistance to earth. c) Check live and neutral connections are correct. d) Check to ensure that when t

Seite 20 - Option B

27 IMPORTANT Adjustments should be made by qualified persons only. If the appliance manufacturer supplies checkout and/or service and maintenance in

Seite 21 - Option C

28 When High and Low pressure settings are correct, replace cap and connect pressure feedback connection (if applicable). Checkout After any adjustm

Seite 22 - Vertical coaxial

29 maximum adjustment screw and hold it on. • If maximum pressure setting needs adjustment turn the maximum rate adjustment screw clockwise for incr

Seite 23 - Electrical panel

3 Section Contents Page No 1.0 Compliance Notices 4 1.1 Certificates of Conformity 5 1.2 General product Information 5 1.3 General Requireme

Seite 24 - 2.7 Gas installation

30 Example: • Potentiometer P2 is set at 0 %, and P3 at 5%, the hold-in voltage of the burner relay is adjustable between 5 % and 100 % of the input

Seite 25 - 3.1 Electrical pre-tests

31 q) Check that the gas pressure remains satisfactory for all appliances on the same circuit. r) Undertake combustion tests checking CO, CO2 and eff

Seite 26 - PRE START DRY RUN

32 4.0 Servicing Warnings It is a requirement that only qualified personnel are allowed to carry out installation commissioning or servicing. In

Seite 27 - Hi-Low regulator

33 Fan and Motor Check that the fan is secure and rotates freely without excessive play in the shaft. The fan blades and motor should be cleaned usin

Seite 28

34 Gas Supply ON Burner fails to light Turn on Gas Supply Electric Supply ON Turn on Electric Supply Air in Gas Supply Purge Gas Line Thermostat call

Seite 29 - Interface board

35 Fault finding cont’d Fan will not run, heater goes off on limit Bad electrical connection Check wiring connection Faulty fan motor or capacitor Ch

Seite 30

36 6. Wiring Diagram 33-68-001 VRA 12-60 VRC 12-30 Auto ignition On/Off WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 31

37 Wiring Diagram 33-68-007 VRC 42 Auto ignition On/Off WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 32

38 Wiring Diagram 33-68-010 VRC 50-60 Auto ignition On/Off WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 33

39 Wiring Diagram 33-68-004 VRA 72-145 Auto ignition On/Off WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 34 - 5.0 Fault finding

4 IMPORTANT NOTICE TO INSTALLERS Installers should satisfy themselves that the gas pipework installation is carried out in accorda

Seite 35 - Fault finding cont’d

40 Wiring Diagram 33-68-013 VRC 72-95 VRE120-145 Auto ignition On/Off WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 36 - CONTROLLER

41 Wiring Diagram 33-68-016 VRC 72-145 3 Phase Auto ignition On/Off WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 37

42 Wiring Diagram 33-68-002 VRA 12-60 VRC 12-30 Auto ignition Hi/Low WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 38

43 Wiring Diagram 33-68-008 VRC 42 Auto ignition Hi/Low WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 39 - WARNING NEUTRAL RESET

44 Wiring Diagram 33-68-011 VRC 50-60 Auto ignition Hi/Low WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 40

45 Wiring Diagram 33-68-005 VRA 72-145 Auto ignition Hi/Low WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 41

46 Wiring Diagram 33-68-014 VRC 72-95 VRE 120-145 Auto ignition Hi/Low WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 42

47 Wiring Diagram 33-68-017 VRC 72-145 3 Phase Auto ignition Hi/Low WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 43

48 Wiring Diagram 33-68-003 VRA 12-60 VRC 12-30 Auto Ignition Modulation WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 44

49 Wiring Diagram 33-68-009 VRC 42 Auto Ignition Modulation WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 45

5 1.0 Compliance notices The Benson Variante range of warm air heaters detailed herewith are manufactured by Benson Heating within a strictly contro

Seite 46

50 Wiring Diagram 33-68-012 VRC 50-60 Auto Ignition Modulation WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 47

51 Wiring Diagram 33-68-006 VRA 72–145 Auto Ignition Modulation WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 48

52 Wiring Diagram 33-68-015 VRC 72-95 VRE 120-145 Auto ignition Modulation WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 49

53 Wiring Diagram 33-68-018 VRC 72-145 3 Phase Auto ignition Modulation WARNING NEUTRAL RESET SEQUENCE CONTROLLER

Seite 50

54 Less Controls Connections On/Off (Hi/Low) 1 Phase 33-64-349T Less Controls Connections On/Off (Hi/Low) 3 Phase 33-67-014T WARNING NEUTRAL RESET WA

Seite 51

55 Less Controls Connections Modulation 1 Phase 33-64-584 Less Controls Connections Modulation 3 Phase 33-67-587 WARNING NEUTRAL RESET WARNING NEUTRA

Seite 52

56 Appliance Type B22 C 32 C12 Electrical Protection IP20 Country Approved Gas Category AT,BG,CH,CY,CZ,DK,EE,ES,FI,GB,GR,HR, IE,IT,IS,LT,LV,NO,PT,

Seite 53

57 NAT GAS / LPG MODEL 12 20 30 42 50 HEAT OUTPUT kW Btu 12.0 40.950 19.6 67,000 29.4 100,000 39.2 134,000 49.0 167,000 HEAT I

Seite 54

58 NAT GAS / LPG MODEL 60 72 95 120 145 HEAT OUTPUT kW Btu 58.8 201,000 72.0 246,000 96.0 328.000 120.0 409,000 144.0 491,000 HEAT

Seite 55

59 Heater Size/ Description 12 30 20 50 42 60 Gas Valve Control Box Pressure Switch Limit Stat 29-01-173 28-30-180 28-40-162 28-16-058 Injector Pr

Seite 56

6 for Machines Specification for General Requirements BS EN 60335 - Part 1 Safety of Household and Similar Electrical Appliances General Requirem

Seite 57 - - models 12-50

60 Ionisation Probe 33-64-194 Burner On Green Neon Overheat Red Neon 28-50-038 28-50-030 Reset Relay 230V 28-25-039 Relay Base 28-25-035 MCB 28-07-0

Seite 58 - - models 60-145

61 Heater Size/ Description 72 95 120 145 Gas Valve Control Box Pressure Switch Gas Valve Fan Control Thermostat Limit Stat Injector Propane Gas I

Seite 59 - 8.0 Parts List

62 33-64-160 Heater Size/ Description 72 95 120 145 Ionisation Probe Burner On Green Neon Overheat Red Neon Reset Relay 230V Relay Base MCB Burner

Seite 60 - Parts list cont’d

63 Model A B C Axial DǾ E F G H J K L M N P Q R 12 440 1050 840.5 80 755 17 640 20 36 60 120 192 277.5 680 103 137 20

Seite 61 - Parts list

64 Model A B C Axial DǾ E F G H J K L M N P Q R 12 440 1050 840.5 80 755 17 500 20 36 60 120 192 277.5 680 103 137 20

Seite 62

65 Model A B C Cent DǾ E F G H J K L M N P Q R S T 12 440 1050 1133.5 80 755 17 640 20 36 60 120 192 277.5 680 103

Seite 63 - 9.0 Dimensions - V

66 Dimensions - Flue 80mm Stainless Steel Flue Fittings. For heater size VR12 - VR20 605mmØ94.4mm494mmØ124.5mm130mm203mm183mm1271mm130mmØ79.7mm Ø80.

Seite 64 - Dimensions - V

67 100mm Stainless Steel Flue Fittings. For heater size VR30 - VR60 605mmØ114.4mm494mmØ149mm140mm249mm220mm1361mm140mmØ99.8mm Ø100.75mm 223mm164mm161

Seite 65

68 130mm Stainless Steel Flue Fittings. For heater size VR72 - VR145 620mmØ144.5mm494mmØ200mm227mm255mm300mm1895mm227mmØ129.7mm Ø130.75mm 252mm193mm1

Seite 66 - Dimensions - Flue

69 Heater A B X Y øZ VRA12 330 105 31 142 125 VRA20 330 105 31 174 125 VRA30 400 175 28 191 150 VRA42 400 175 28 300 150 VRA50 40

Seite 67 - For heater size VR30 - VR60

7 to during foreseen normal use when installed in accordance with the manufacturers recommendations. 1.3 General Requirements Caution Before

Seite 68 - For heater size VR72 - VR145

70 Heater A B X Y øZ VRC12 653 755 31 142 125 VRC20 653 755 31 174 125 VRC30 653 755 28 261 150 VRC42 653 755 28 200 150 VRC50 65

Seite 70

72 Document reference number 33-64-695 Apr 2013 issue 12 Technical Support: Tel: 01384 489 200 Fax: 01384 489 707 [email protected] www.

Seite 71

8 The warranty commences from the date of dispatch from the manufacturer, and is subject to the terms detailed within the Benson Heating 'condi

Seite 72

9 Additionally the maximum temperature within the plant room should not exceed 32°C 2.0 Installation The location chosen for the heater must al